The BACnet MS/TP module with 4 digital triac outputs was developed for decentralized switching tasks. It is suitable for switching electrical components, such as relays, contactors, HLK valves, etc. The outputs can be switched by means of standard objects via a BACnet client. In addition, the outputs can be overridden manually by means of switches on the device. The module is addressed and the baud rate is set by means of two address switches on the front. Suitable for decentralized mounting in serial sub-distributor.
Protocol - BACnet MS/TP
Addressing range - 00 to F9
Bus interface - RS485 (two-wire bus)
Transmission rate - 9600 to 115200 baud
Operating voltage range - 20 V to 28 V AC/DC (SELV)
Current consumption - 100 mA (AC) / 40 mA (DC)
Relative duty cycle - 100%
Output / contacts - 4 digital outputs (triac)
Output / switching voltage - 24 V AC up to max. 250 V AC
Output / continuous current - 0.5 A / output
Output / switching current - 0.8 A (less than 30 s)
Output / switch-on current - 10 A (less than 20 ms)
Display - Green, red and yellow LED
Dimensions (W x H x D) - 35 x 70 x 75 mm
Weight - 95 g
Operating temperature range - (-5 °C to +55 °C)
Storage temperature range - (-20 °C to +70 °C)
Ingress protection for housing / terminal block - IP40 / IP20
Technical Data
P/N - 11088013
Color - gray
Feature 1 - 4x OUT (triac)
Feature 2
EAN-No - 4250184138693