The LON three-point module with 6 digital inputs, 2 two-level relay outputs and 2 digital outputs was developed for decentralized switching tasks. It is suitable for switching, for example, multi-level pumps, fans, burners or similar. With strong inductive loads, we recommend protecting the relay contacts additionally with an RC element. The inputs and outputs are scanned and activated by SNVT network variables. The input terminals 1 to 6 are wired with the C2 terminals on two poles to potential-free switches or contacts. The module has a manual control for the outputs, which is activated only in configured mode. Suitable for decentralized mounting in serial sub-distributor.
Protocol - TP/FT-10, free topology
Neuron - FT5000
Transmission rate - 78 KBit/s
Operating voltage range - 20 V to 28 V AC/DC (SELV)
Current consumption - 220 mA (AC) / 90 mA (DC)
Relative duty cycle - 100%
Recovery time - 550 ms
Inputs - 6 x digital contacts
Input / switching threshold - 4.5 V DC
Outputs (relay) - 2 x two-level
Output / switching voltage - 250 V AC
Output / current - 6 A / output
Outputs (digital) - 2 NO (photoMOS)
Output / switching voltage - 40 V AC/DC
Output / current - 100 mA
Operation and bus display - Green and yellow LED
Dimensions (W x H x D) - 50 x 70 x 75 mm
Weight - 126 g
Operating temperature range - (-5 °C to +55 °C)
Storage temperature range - (-20 °C to +70 °C)
Ingress protection for housing / terminal block - IP40 / IP20
Technical Data
P/N - 11085913
Color - green
Feature 1 - 6x IN (contact)
Feature 2 - 2x OUT (relay CO), 2x OUT (opto NO)
EAN-No - 4250184135814