The Modbus three-point module with 6 digital inputs, 2 two-level relay outputs and 2 digital outputs was developed for decentralized switching tasks. It is suitable for switching, for example, multi-level pumps and fans or louvers. With strong inductive loads, we recommend protecting the relay contacts additionally with an RC element. The inputs and outputs can be switched and scanned by means of standard objects via a Modbus master. The input terminals 1 to 6 are wired with the C2 terminals on two poles to potential-free switches or contacts. The module has a manual control for the outputs. The module address, the baud rate and the parity are set by means of two address switches on the front. Suitable for decentralized mounting in serial sub-distributor.
Protocol - Modbus RTU
Addressing range - 00 to 99
Bus interface - RS485 (two-wire bus)
Transmission rate - 1200 to 115200 baud
Operating voltage range - 20 V to 28 V AC/DC (SELV)
Current consumption - 100 mA (AC) / 40 mA (DC)
Relative duty cycle - 100%
Inputs - 6 x digital contacts
Input / switching threshold - 4.5 V DC
Outputs (relay) - 2 x two-level
Output / switching voltage - 250 V AC
Output / current - 6 A / output
Outputs (digital) - 2 NO contacts (photoMOS)
Output / switching voltage - 40 V AC/DC
Output / current - 100 mA
Display - Green, red and yellow LED
Dimensions (W x H x D) - 50 x 70 x 75 mm
Weight - 126 g
Operating temperature range - (-5 °C to +55 °C)
Storage temperature range - (-20 °C to +70 °C)
Ingress protection for housing / terminal block - IP40 / IP20
Technical Data
P/N - 11083813
Color - gray
Feature 1 - 6x IN (contact)
Feature 2 - 2x OUT (relay CO), 2x OUT (opto NO)
EAN-No - 4250184161004