The Modbus module in an IP65 housing with 4 digital inputs and 2 relay outputs was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 motorized fire dampers. With strong inductive loads, we recommend protecting the relay contacts with an RC element. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard objects via a Modbus master. The module address, the baud rate and the parity are set by means of two address switches.
Protocol - Modbus RTU
Addressing range - 00 to 99
Bus interface - RS485 (two-wire bus)
Transmission rate - 1200 to 115200 baud
Operating voltage range - 20 V to 28 V AC/DC (SELV)
Current consumption - 200 mA (AC) / 75 mA (DC)
Relative duty cycle - 100%
Inputs - 4 x digital
Input / voltage - 30 V DC
Input / high signal - more than 8 V AC/DC
Output / contacts - 2 changeover contacts (DPST)
Output / switching voltage - 250 V AC
Output / continuous current (UL) - 8 A / output
Output / continuous current (VDE) - 10 A / output
Output / switch-on current - 80 A (less than 20 ms)
Display - Green, red and yellow LED
Dimensions (W x H x D) - 159 x 41.5 x 120 mm
Weight - 350 g
Operating temperature range - (-5 °C to +55 °C)
Storage temperature range - (-20 °C to +70 °C)
Ingress protection for housing / terminal block - IP65 / IP20
Technical Data
P/N - 1108331326IP
Color - gray
Feature 1 - 4x IN (U or contact)
Feature 2 - 2x OUT (relay CO)
EAN-No - 4250184135630